KWN Series Water-Cooled Industrial Chiller

Compact Design · Stable Performance · Easy Installation

Product Overview

The KWN Series uses Panasonic or Danfoss hermetic scroll compressors for stable performance and long service life. It features a high-efficiency shell-and-tube condenser and SUS304 stainless steel coil-in-tank evaporator. The integrated hydraulic module includes a SUS304 water tank, high-flow pump, and Bangpu microcomputer control system.

How It Works


Chilled water absorbs process heat and returns to the evaporator. The refrigerant absorbs heat and evaporates. The scroll compressor raises pressure and temperature. The shell-and-tube condenser rejects heat to cooling water, which is cooled by a cooling tower. The expansion valve reduces pressure, and the cycle repeats.

1. Evaporation

SUS304 coil-in-tank evaporator transfers process heat to refrigerant.

2. Compression

Hermetic scroll compressor raises refrigerant pressure and temperature.

3. Condensation

Shell-and-tube condenser rejects heat to cooling water.

4. Expansion

Expansion valve reduces pressure and returns refrigerant.

Water-cooled design requires a cooling tower or cooling water source; it offers stable heat rejection and lower noise.

Technical Specification

Model Cooling Capacity (KW) Total Power (KW) Chilled Water Flow (m³/h) Dimensions L×W×H (mm)
50HZ 60HZ
KWN-03 9.2 11.3 3.05 1.6 950 × 500 × 990
KWN-05 15 17.9 4.05 2.6 950 × 500 × 990
KWN-06 17.7 21.5 5.4 3 950 × 500 × 990
KWN-08D 23.6 28.3 6.9 5.2 1180 × 700 × 1325
KWN-10D 30 36 8.1 6 1180 × 700 × 1325

* Showing partial models. Download the catalog for full KWN specifications up to 337.9KW.

Standard parameter are listed above. Customized designs are available. Please consult our sales engineers for details.

Key Components


Hermetic Scroll Compressor

Panasonic or Danfoss scroll compressor for stable performance.

Shell-and-Tube Condenser

High-efficiency water-cooled condenser for stable heat rejection.

SUS304 Tank Evaporator

SUS304 stainless steel tank with coil evaporator.

Bangpu Microcomputer Control

Integrated hydraulic module and high-flow pump.

Download Technical Documents


NEWIN Water Cooled Chiller Product Catalog

Click & Download: The complete Water-cooled Industrial Chiller catalog covering series overview, specifications, components, operation, installation, and drawings.

Got Questions? We’ve Got Answers!

Have specific requirements for your cooling project? Explore our frequently asked questions below, or contact our engineering team for tailored selection support.

Does the KWN Series require a cooling tower?
Yes. Water-cooled chillers use a shell-and-tube condenser and require a cooling tower or a central cooling water system to reject heat.
The typical entering cooling water temperature is 30°C, with an outlet of 35°C. Please confirm based on your local conditions.
It features a Bangpu microcomputer control system with clear fault codes, and integrated hydronic kit for easy installation.
No. Reducing the pipe diameter increases resistance, reduces flow, and can cause high-pressure overload and higher power consumption.
Standard models operate at 5°C+. Below 0°C requires customization (glycol/brine) and should be specified during selection.